Ametek AN-3100D Installation And Configuration Manual page 17

Table of Contents

Advertisement

Item 12 Window Legends
TP
Legends printed on Transparency Film (field
changeable)
E
Legends Engraved on Windows
Note:
Window engraving or printed legends can be
provided at the factory at no charge if provided 1 week before
shipment.
Item 13 Communications
SPT
Serial Port RS-232/485 (field selectable)
Used with Communication Protocol Option:
SIM, MB, DNP or SD
ETH
Ethernet Port (RJ45)
Used with Communication Protocol Option:
SIM, MB, DNP and WEB
NR
No Communications Required
Can select both SPT and ETH for dual communications
Item 14 Communication Protocols
SIM
Modbus Communications, Receive Alarms Only. No
Field Contact Inputs. Can be used with Serial port
(Option SPT), and Ethernet (Option ETH)
MB
Modbus Bidirectional Communications.
Transmit or Receive alarms. Can be a mixture of
Modbus generated alarms or field contact inputs.
Modbus RTU used for Serial Port (Option SPT),
TCP-IP used for Ethernet, (Option ETH)
DNP
DNP 3.0 Communications, Transmit Alarms.
Can be used with Serial port (Option SPT), and
Ethernet (Option ETH)
SD
Serial ASCII Data Output of Time Stamped Alarms
Used with the Time Stamping option SER or
SERFR, and the Serial port (Option SPT)
Item 15 Options
FR
1 msec Input Response (50 msec
Standard)
(This will capture alarms that last 1 msec
or longer. If Time Stamping is required,
select option SER instead)
SER
Time Stamping of alarms (4 ms resolution)
(Each alarm is accompanied with a time
stamp, containing point #, alarm state, time
& date. The Time Stamp output can be
selected as Serial ASCII Data to a printer
or terminal [must select option SD],
Modbus [must select option MB] or DNP
[must select option DNP]. )
SERFR
Time Stamping of alarms (1 ms resolution)
(Each alarm is accompanied with a time
stamp, containing point #, alarm state, time
& date. The Time Stamp output can be
selected as Serial ASCII Data to a printer
or terminal [must select option SD],
Modbus [must select option MB] or DNP
[must select option DNP]. Option limited to
25 Cells)
IB
IRIG-B Time Sync Input (used with SER
Option)
(Standard BNC Input)
Item 15
Options (continued)
AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
SP
Serial Printer used for Time Stamped
Alarms
(Used with SER option [time stamped
alarms] and SD option [serial data output].
Modbus, DNP and Ethernet are not
available when selecting this.)
GF
Ground Fault Detector (internally
mounted)
For 24, 48, 125VDC Field Contact Voltage
(options X, D, XC, DC, TC)
RLY
Additional Two CSM Common Relays
(Base system includes 2 CSM Common
Relays configurable for Critical or Non-
Critical Horn, Ringback Horn. The
additional 2 CSM Common Relays can be
configured for additional horns or
Critical/Non-Critical Reflash or Fault,
Power Fail, System Watchdog, or Ground
Fault Detect)
SW
External Inhibit Switch Input
(Software configurable for inhibit of LED
Lamps, Horn, Repeat Relay Outputs or
CSM Common Relay Outputs)
HN
Internal Horn
AS
Automatic Horn Silence
(Can be used to silence any horn with
software configurable delay up to 60
seconds, in 0.25 second increments.
Independent setting for internal or external
horns)
FS
Flash Synchronization. Synchronizes the
flash rate to remote displays. Needs to be
specified for each Annunciator that will be
synchronized together. (Requires wiring
between Annunciator Systems.)
CE
CE Certification
CE Certification available for all
configurations except for FCV options D,
DC, D/ISO, Y/ISO.
In these cases, a NEMA Enclosure (option
N4, N4PB) or Front Cover (option NCB,
NCT) is required. 120/230VAC & 125VDC
Input Power provided via External
Supplies unless the NEMA Enclosure or
Front Cover is used.
STM
Moisture/ Fungus Proof Coating
FM
FM Class 1, Div.2 Groups A,B,C,D
Certification
FM Certification available for all
configurations. A NEMA Enclosure (option
N4, N4PB) or Front Cover (option NCB,
NCT) is required. Power option A
(230Vac), B(120Vac), C(125Vdc), (see
ITEM 10), is provided via External
Supplies only.
i.
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents