Controls

Pushbuttons
Integral Pushbutton Option (INTB):
(4) External Pushbutton Inputs: Test, Acknowledge, Silence and Reset
5VDC @0.002 mA per Pushbutton
(provided by Annunciator)
Switch Input (Option SW)
Software configurable for:
Inhibit of LED Lamps, Horn, Repeat Relay Outputs or CSM Common Relay
Outputs
5VDC @0.002 mA (provided by Annunciator)

System Relays

Alarm Grouping
Critical or Non-Critical Alarms: Selectable in software per input
Used to provide separate horns, or other relay outputs
Critical Alarms have priority over Non-Critical (can be disabled)
Standard Relays
(2) Relays Software Configurable for:
Critical or Non-Critical Horn, Ringback Horn
Energized or De-Energized Relay Coil, selectable in Software
Form A or Form B (N.O. or N.C.) Contact, Selectable by Jumper
Optional Relays (Option RLY)
(2) Additional Relays Software Configurable for:
Critical or Non-Critical Horn, Ringback Horn, Critical or Non-Critical Reflash,
Critical or Non-Critical Fault, Power Fail, System Watchdog, or Ground Fault
Detect)
Energized or De-Energized Relay Coil, selectable in Software
Form A or Form B (N.O. or N.C.) Contact, Selectable by Jumper
Relay Ratings:
24VDC @ 3.0 Amps
110VDC @ 0.1 Amps
120VAC @ 3.0 Amps
Resistive Load

Audible Devices

Internal 80db @ 30cm audible device (option HN)
External Audible Devices available
98
Test, Acknowledge, Silence and Reset
AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL