Onnecting Ower; 120/230 Vac & 125Vdc Input Power; Field Contact Voltage - Ametek AN-3100D Installation And Configuration Manual

Table of Contents

Advertisement

C
ONNECTING
The AN-3100D Annunciator operates from a selection of AC and DC Voltages.
The Annunciator uses Power Supplies to provide the necessary 5VDC Logic and
LED Power. If the Field Contact Voltage (FCV) needs to be provided from the
Annunciator, separate FCV Supplies are provided.
For 24 and 48 VDC Input Power, an Integral Power Supply will always be used.
In some cases, multiple supplies will be located in the system to accommodate
the quantity of inputs specified.
For 120/230 VAC and 125 VDC Input Power, the quantity of inputs, window
sizes and other options determines whether the Power supplies can be self
contained within the Annunciator (Integral Power Supply) or external to the
Annunciator. External power supplies shall be Class 2.
120/230 VAC & 125VDC Input Power
Annunciator Window
Size
Full
(1 per Cell)
Half
(2 per Cell)
Third (3 per Cell)
Quad (4 per Cell)
The Field Contact Voltage (FCV) can be provided externally by the user or can
be provided by the Field Contact Voltage Supply.

Field Contact Voltage

Customer
Input Power
24 VDC
48 VDC
125 VDC
120 / 230 VAC
AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
P
OWER
Integral Power Supply
# of Inputs
(with Repeat
Relay option)
1-25
1-43
1-56
1-60
Customer Supplied
12, 24, 48, 125VDC
X
X
X
X
External Power Supply
# of Inputs
# of Inputs
(without Repeat
(with Repeat
Relay option)
Relay option)
1-30
>25
1-60
>43
1-90
>56
1-100
>60
Annunciator Supplied
Field Contact Voltage
24 VDC
125 VDC
X
X
X
X
X
X
i.
# of Inputs
(without Repeat
Relay option)
>30
>60
>90
>100
45