Common Dnp Configuration Settings - Ametek AN-3100D Installation And Configuration Manual

Table of Contents

Advertisement

Common DNP Configuration Settings

IED Address
This is a number used to identify the recorder on the network (range 1 - 65534).
Transmission delay
This is the time to disable the master transmitter on an RS485 network (range 0
- 65535) (not currently used).
Data Link Confirm
This can be set as Never, Sometimes or Always. The default value is Never.
Retries
This is the number of times the recorder will retry to connect if Data Link
confirmation is required (range 0 - 255)
Timeout
This is the time the IED will wait for a Data Link confirmation. Valid numbers are
0 - 65535.
Select/Operate arm time
This is the time period after the select command is received that the operate
command will be performed (range 0 - 65535) (Not currently used)
92
AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents