Common Service Wiring (With I/O Modules) - Ametek AN-3100D Installation And Configuration Manual

Table of Contents

Advertisement

Common Service Wiring
(with I/O Modules)
FULL SIZE WINDOW
(1 I/O Card)
Terminal Block
Common Service
Relay Wiring
TB3
1
CSM Relay #1
(Form A or B)
2
3
CSM Relay #2
(Form A or B)
4
5
CSM Relay #3
(Form A or B)
6
Option
RLY
7
CSm Relay #4
(Form A or B)
8
Input / Relay Wiring
TB1
1
Input 1
+ FCV
2
Input 2
3
- FCV
4
Option RR
5
Single Repeat Relay
Per Input (Form A or B)
6
Option RR
7
Single Repeat Relay
Per Input (Form A or B)
8
NOTE: When wiring an external horn or other audible device to the CSM output relays,
it is recommended that the interconnect wires be physically isolated from any other
input or output wiring.
44
Model Code
NPB
OR
Pushbutton/Switch
Terminal Block TB4
Input
TB1
TB4
TB3
TB1
1
1
2
2
3
3
J2
4
4
5
5
J1
6
6
7
7
8
8
CSM Terminal Block Assembly
(rear view)
Pushbutton / Switch Wiring
CSM Relay K1
CSM Relay K2
CSM Relay K3
+ LED Flash Synchronization
CSM Relay K4
- LED Flash Synchronization
Shown w/common FCV
Shown w/Isolated FCV
+(L)
24,48,125 VDC
120VAC, 60Hz
-(N)
Customer FCV
Repeat Relay
for Input #1
Repeat Relay
for Input #2
HALF SIZE WINDOWS
(1 I/O Card)
CSM Relay
Terminal Block TB3
1
2
3
4
5
6
7
8
TB4
Common Return
1
Silence
2
Acknowledge
3
Test
4
Reset
5
Configurable Input
6
(option SW)
7
8
Note: TB4-7 can be used as a second Configurable
Input when the LED Flash Synchronization Option is not used.
Communications Wiring
Connector
1
2
DB9 (F)
3
4
J1
5
6
7
8
9
Connector
AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
Customer
Pushbuttons
To other Annunciator + LED Sync
To other Annunciator - LED Sync
RS-232
RS-485
Transmit
TX/RX -
Receive
TX/RX +
Ground
Ground
RTS
RJ 45
J2
Ethernet

Hide quick links:

Advertisement

Table of Contents
loading