System Configuration And Set-Up - Ametek AN-3100D Installation And Configuration Manual

Table of Contents

Advertisement

S
C
YSTEM
ONFIGURATION AND
The AN-3100D Annunciator is already factory configured per the model number.
Most of the configuration of the system is made using software, however some
settings such as relay contact arrangement (Form A or Form B) needs to be
configured by the user. The default configurations are specified below:
Item
Inputs
Optional
Repeat Relays
CSM Functions Auxiliary Contact Output Type
Serial
Communication
Module
* NO/NC Field Inputs can be configured via the software or hardware, but
not both. Choose one method only.
6
N.O. (normally open), N.C. (normally
closed) Field Contact Inputs
Field Contact Voltage
(12, 24, 48, 125VDC, 120VAC)
OR
(24-125VDC)
Common FCV (field contact voltage)
or Isolated FCV
Input Module Address Setting
Operational Sequence (A, M, etc)
Sequence Grouping
Input Response
Critical/Non-Critical Assignment
Form A (normally open), Form B
Contacts (normally closed)
Form C Contacts (SPDT)
Energized or De-Energized Relays
Repeat Relay Operation
(Form A, Form B)
Auxiliary Contact Output Mode
(Energized or De-Energized)
Auxiliary Contact Output Operation
(Horn, Reflash, Fault, Watchdog,
Power Monitor, Ground Fault)
Other system-wide functions
RS-232 , RS-485
RS-485 Termination Jumper
Flash Synchronization (master/slave)
S
-U
ET
P
Default
Setting
N.O.
Factory
Configured
Per Model
Number
1 group
50 msec
Non-Critical
Form A
Factory
Configured
Per Model
Number
De-Energized Software
Follows Input
Form A
De-Energized Software
Critical Horn
& Non-Critical
Horn
None
Selected
RS-232
Out
Master
AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
Configuration
Method
Software or
Hardware *
Hardware
Hardware
Hardware
Software
Software
Software
Software
Hardware
Hardware
Software
Hardware
Software
Software
Software
Software
Hardware