Event Data

Event data may be read in blocks of 10 events at a time. These appear in a
block of 60 registers (6 per event) located at the configured Start Address plus
1000 i.e. if the Start Address is set to 40001 then the events appear at 41001-
41060. Once ten events are read then the registers are reloaded with any
subsequent ones from the 500 event buffer. If no event has occurred, then all 12
bytes are filled with FF HEX.
The event data format is as shown below:
Word
1
2
3
4
5
6
An example of the register format for the 10 events is shown below:
Event Data
41001
1st Event
41002
41003
41004
41005
41006
41007
2nd Event
41008
41009
41010
41011
41012
41054
10th
Event
41056
41057
41058
41059
41060
* Supports Master or Slave Mode, Transmit only
112
MSB
Year
Day
Minute
Millisecond (0-999)
0x00
IRIG-B Sync
Year (0-99) high byte / Month (1-12)low byte
Day of month (1-31)high byte /Hours (0-23) low byte
Minutes (0-59) high byte / Seconds (0-59) low byte
Milliseconds (0-999) two bytes
AN-3100D Point Number (1-198)
IRIG-B Sync – high byte / Point Status (1 = A, 0 = N) low byte
Year (0-99) high byte / Month (1-12)low byte
Day of month (1-31)high byte /Hours (0-23) low byte
Minutes (0-59) high byte / Seconds (0-59) low byte
Milliseconds (0-999) two bytes
AN-3100D Point Number (1-198)
IRIG-B Sync – high byte / Point Status (1 = A, 0 = N) low byte
Year (0-99) high byte / Month (1-12)low byte
Day of month (1-31)high byte /Hours (0-23) low byte
Minutes (0-59) high byte / Seconds (0-59) low byte
Milliseconds (0-999) two bytes
AN-3100D Point Number (1-198)
IRIG-B Sync – high byte / Point Status (1 = A, 0 = N) low byte
LSB
Month
Hour
Second
Input Point No.
1 = Point on
0 = Point off