Sequence
The alarm sequence for each input group is defined in this page. The Input
Configuration page was used to indicate which of the four available groups was
assigned to each input. This page identifies the sequence chosen for each
group.
Note: The four available groups can be set up for the same First-Out Sequence,
but each group is treated separately as its own first out group.
To change the alarm sequence, click on the entry then choose the sequence
from the list. The alarm sequences shown below follow ISA Standard S18.1 –
1979 (R.1985).
ISA-A
ISA-A-4
ISA-A-4-5-6
ISA-M
ISA-F1A-1
ISA-F2A-1
ISA-F2M-1
ISA-F3A
ISA-F3M
ISA-F3C
ISA-FFAM2
ISA-R
ISA-RC
ISA-R-12
ISA-R-12C
78
Automatic reset with lock-in of alarms
Automatic reset with no lock-in of alarms
Automatic reset, non-locking, no flash, no audible, NO PB
Manual Reset with lock-in of alarms
First Out Flash, Subsequent alarm steady, auto reset
First Out, Fast Flash, auto reset
First Out, no subsequent alarm flash, manual reset
First Out, triple flash, first out reset
First out, triple flash, first out manual reset
First out, triple flash, dual color, manual reset
First Out, manual reset
Ringback, separate flash for return to normal
Ringback, separate color for return to normal
Automatic Momentary Ringback, dual flash, manual reset
Ringback, dual color flash, manual reset
AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL