Reference Manual
00809-0100-5901
Configure Calibration Distance using TankMaster
The cone antenna extension causes a small offset error that needs to be calibrated away by
adjusting the Calibration Distance parameter.
Procedure
1. Start the Rosemount
2. In the WinSetup workspace, right-click on the device icon.
3. Select Properties and open the Geometry tab.
4. Enter the appropriate Calibration Distance:
Rosemount 5900C Radar Level Gauge
™
TankMaster
•
For a 4-in. cone the calibration distance is about 2 mm for each 100 mm
extension
•
For a 6-in. cone the calibration distance is about 1 mm for each 100 mm
extension
•
For an 8-in. cone the calibration distance is 0
™
WinSetup configuration software.
Installation
September 2019
™
WinSetup
89