Table C-3: Definitions of Analog Input Function Block System Parameters
Index Number Parameter
19
FIELD_VAL
20
UPDATE_EVT
21
BLOCK_ALM
22
ALARM_SUM
23
ACK_OPTION
24
ALARM_HYS
25
HI_HI_PRI
26
HI_HI_LIM
27
HI_PRI
28
HI_LIM
29
LO_PRI
30
LO_LIM
31
LO_LO_PRI
32
LO_LO_LIM
33
HI_HI_ALM
34
HI_ALM
35
LO_ALM
36
LO_LO_ALM
37
OUT_D
300
Units
Description
Percent
The value and status from the transducer block or from the
simulated input when simulation is enabled.
None
This alert is generated by any change to the static data.
None
The block alarm is used for all configuration, hardware, connection
failure or system problems in the block. The cause of the alert is
entered in the subcode field. The first alert to become active will set
the Active status in the Status parameter. As soon as the
Unreported status is cleared by the alert reporting task, another
block alert may be reported without clearing the Active status, if
the subcode has changed.
None
The summary alarm is used for all process alarms in the block. The
cause of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status parameter. As
soon as the Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing the Active
status, if the subcode has changed.
None
Used to set auto acknowledgment of alarms.
Percent
The amount the alarm value must return within the alarm limit
before the associated active alarm condition clears.
None
The priority of the HI HI alarm.
EU of
The setting for the alarm limit used to detect the HI HI alarm
PV_SCALE
condition.
None
The priority of the HI alarm.
EU of
The setting for the alarm limit used to detect the HI alarm
PV_SCALE
condition.
None
The priority of the LO alarm.
EU of
The setting for the alarm limit used to detect the LO alarm
PV_SCALE
condition.
None
The priority of the LO LO alarm.
EU of
The setting for the alarm limit used to detect the LO LO alarm
PV_SCALE
condition.
None
The HI HI alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
None
The HI alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
None
The LO alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
None
The LO LO alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
None
Discrete output to indicate a selected alarm condition.