Table 6-10: RECOMMENDED_ACTION
Alert Type
Host Diagnostic
Message
Device Warning
Maintenance
Device Minor
Required
Information
Function Check
Check function
Rosemount 5900C Radar Level Gauge
(continued)
Description
Measurement values can not be
retrieved. Last good value with a BAD
status is displayed. Field repair might
be possible.
Unexpected measurement values
retrieved due to configuration related
problem.
Transducer Block is not in Auto Mode
Service and troubleshooting
September 2019
Recommended Action
1. Restart the level measurement.
2. Cycle power to the device by
disconnecting the FF bus.
3. Factory reset measurement
configuration and reconfigure
device.
4. If error persists, contact Emerson
Automation Solutions/
Rosemount Tank Gauging
department.
1. Check configuration of the
device.
See Device Status for more
information on the error source (see
Viewing device status in AMS Device
Manager).
Regular preparation work is in
progress. One or more Transducer
Blocks are in Out of Service mode.
1. Return Transducer Block to Auto
mode.
241