Emerson Rosemount 5900C Reference Manual page 229

Radar level gauge
Table of Contents

Advertisement

Reference Manual
00809-0100-5901
Table 6-1: Troubleshooting Chart for the Rosemount 5900C
Symptom
The level gauge
configuration can not be
saved
6.3.1
Device status
Table 6-2
2410 Tank Hub, or in the Rosemount TankMaster program. Device status can be found in
Input register 4000. See
information on how to view Input registers.
Table 6-2: Device Status Messages
Message
Running Boot Software
Device Warning
Device Error
BOOT Beta Version
APPL Beta Version
Level correction error
Rosemount 5900C Radar Level Gauge
Possible cause
Disturbing objects in the
tank
The gauge is write protected
shows device status messages that may appear on the display of the Rosemount
Viewing input and holding registers using TankMaster
Description
The application software could not
be started.
The application SW is not loaded in
the flash memory
The previous upload of the flash
SW failed
A device warning is active.
A device error is active.
Beta version of boot program used
Beta version of application program
used
The LPG module is enabled but the
module is either incorrectly
configured, or there is no sensor input
data for pressure or temperature.
(continued)
Action
Check that the Rosemount 5900C has not locked on an
interfering object in the tank
Use the Tank Scan function in Rosemount TankMaster
WinSetup to analyze the measurement signal: - Check
if there are any disturbing echoes from obstacles in the
tank - Check if there is a strong echo at the bottom of
the tank; use deflection plate at the end of still pipe.
See the Rosemount Tank Gauging
Configuration
Manualfor more information on how to
use the Tank Scan function
Check position of the write protection switch and make
sure that it is in the OFF position, see
switch.
Check write protection setting in Rosemount
TankMaster WinSetup, see
TankMaster
.
Action
Reprogram the gauge with new
software.
Contact Emerson Automation
Solutions /Rosemount Tank Gauging
service department.
See
Warning messages
See
Error messages
Ensure that approved software is used
Ensure that approved software is used
See Input register 4702 LPGIregArea-
LPG_Corr_Error for more information.
Service and troubleshooting
September 2019
System
Write protection
Write protection using
for more
for details.
for details.
229