Reference Manual
00809-0100-5901
5. Repeat for each device to be programmed. Use the Remove button if you wish to
6. Click the Browse button to locate the flash program file. File extension *.cry is used
7. Click the Start Programming button.
8. Click the Start Programming button to activate device programming.
9. Update the TankMaster installation by adding new *.ini files for the Rosemount
Rosemount 5900C Radar Level Gauge
change the list of devices to be programmed.
for these files.
Now the Start Device Programming window appears.
If a Rosemount 2460 System Hub is used, a maximum of 25 devices can be
programmed. If there are more devices the programming must be divided in two
steps.
5900C gauge to the TankMaster installation folder:
Two *.ini files are used for the Rosemount 5900C, RLG.ini and RLG0xx.ini, where xx
is the identification code of the application software.
a) Copy the RLG.ini file to the C:\Program Files\Rosemount\Server
folder.
b) Copy the RLG0xx.ini file to the C:\Program Files\Rosemount\Shared
.
folder
Service and troubleshooting
September 2019
217