I/O Link overruns corrective actions

Depending upon the application, one or more of the following actions may be appropriate.
Avoid using IOP resident parameters other than:
Analog Input scan parameters PV and PVSTS.
all alarm flags such as BADPVFL, PVHHFL, PVHIFL, PVLOFL, PVLLFL, PVROCPTP and
PVROCNTP.
Digital Input scan parameters PVFL and BADPVFL.
Digital Output scan parameters SO and INITREQ.
Change the point mix or scan rate to redistribute or slow down points that read multiple non-scan
I/O Link parameters.
Use Logic points for non-scan I/O input connections that are used by more than one point.
Delete inactive or non-essential points and non-scan input connections that are used by more than
one point.
Contact the Honeywell Technical Assistance Center for additional help if the above recovery actions are
not useful.

Comm/Control Hard failure codes

The following the following table defines the Hard failure codes for both the HPMM Communications
and the Control processors. This table spans numerous pages. Some codes are used for both the
Communications and Control processors where others are unique to an individual processor. The CPU
column in the table indicates Both, Comm, or Control to make the distinction.
Corrective actions are identified by number. The corrective actions are listed in Table 57 HPMM
Corrective Actions.

Table 58 Communications and Control Processor Hard Failure Codes

Error
CPU
Code
0000
Both
0001
Both
0002
Both
0003
Both
0004
Both
0005
Both
0006
Both
0007
Both
0008
Both
0009
Both
000A
Both
000B
Both
000C
Both
000D
Both
R688
December 2020
Failure Mnemonic
NULL
Unknown Error
PWRDWN
Power Down Detected
LR_PAR
Local RAM parity error
LR_LRAM
Unused on HPM Platform
LR_CK
Unused on HPM Platform
LR_EXC
Unused on HPM Platform
LR_HREV
MM_HREV
LR_TMR
LR_PTRN
Local RAM pattern test failure
LR_BYTE
Unused on HPM Platform
LR_ADCD
LR_ADDL
LR_CLRR
Local RAM initialization test failure
HPM High-Performance Process Manager Service
Honeywell
4.3 Fault Isolation Concepts
Description
4 Fault Isolation
Corrective Action
(See Table 57)
2
2
2, 6
1
1
1
6
1
6