Figure 211 Full Scale Calibration Circuit - Tc And All Linear Full Scale Circuits - Honeywell HPM Service

High-performance process manager
Table of Contents

Advertisement

Figure 211 Full Scale Calibration Circuit – TC and All Linear Full Scale Circuits
Model MU/MC-TAIL01 and MU/MC-TAIL02 FTAs
R688
December 2020
Cu
NC
+
-
Cu
Channels 2-8
+
-
Model MU/MC-TAIL03 FTA
Cu
NC
+
-
Cu
Channels 1-8
User Input Device
Input Voltage:
0-100 mV dc
0-5 volt
Current Input:
4-20 mA
10-50 mA
Themocouple: A NSI J
ANSI K
A NSI E
A NSI T
A NSI B
A NSI S
A NSI R
Japanese Type R
HPM High-Performance Process Manager Service
1
A
2
B
3
C
4
Cu
17
Cu
Channel 1
Use copper (Cu) w ire f rom voltage source.
A
B
P1
C
1
Install the jumper betw een pins 2 and 3.
Full-Scale Calibration Values
Normal Range
100 mV
5 V
20 mA (5 V)
50 mA (5 V)
40 mV
40 mV
40 mV
40 mV
20 mV
20 mV
20 mV
20 mV
Honeywell
7 IOP Calibration Procedures
7.4 LLAI IOP Calibration Procedure
TB1
A
B
C
Shield
TB2
Ref erence
2
3
Extended Range
N/A
N/A
N/A
N/A
100 mV
40 mV
100 mV
40 mV
20 mV
20 mV
20 mV
20 mV
441