4 Fault Isolation

4.13 Power System Indicators

Card Type
Indicator
Serial Interface
Power
Status
4.13 Power System Indicators

Standard Power System

SHOCK HAZARD
Troubleshooting, opening this equipment and removing any panels or covers
will expose the user to the risk of a shock hazard. There are no user
serviceable parts inside this equipment. Refer all servicing only to qualified
service personnel.
Examine the DC Out, Battery, Fan/Temp, AC In, and Charging indicators for each Standard Power
Supply module. The Standard Power System cover, illustrated by the following figure, identifies the
LED indicators. If the Power system is fully functional, all five of the indicators are Illuminated.

Figure 186 Standard Power System Indicators

DC Ou t
Ba ttery
382
Indicates that power is present on the FTA.
One of the following indicator status conditions exists. The conditions are listed in
the order of importance.
Not lit: This condition exists only when the FTA is in a
Slow blink: This condition indicates that the FTA has not (Symmetrical 1 sec.
blink)
received a Time Out Gate (TOG) refresh from the
seconds.
Fast blink: This condition indicates that one or more Array (Symmetrical .5 sec.
blink)
Points configured for this FTA have a
Odd blink: This condition indicates that one or more Array (Asymmetrical 1/.25
sec. blink) Points configured for this FTA have an error in
configuration error category.
The IOP/HPMM is not configured or configured improperly.
Constantly lit: This condition indicates that no errors exist in the FTA.
Due to the long ACK/Message timeout time and the required three tries, the FTA
may indicate a TOG timeout if the CIM is responding with an ACK to the FTA
requests, or if the destination PLC device is not responding to the requests.
Additional troubleshooting information can be found in the Serial Interface
Options manual.
Supply 1
Fa n/Temp
AC In
Ch argi ng
HPM High-Performance Process Manager Service
Honeywell
Functionality
Supply 2
DC Ou t
Ba ttery
Fa n/Temp
AC In
Ch argi ng
Hard failure state.
SI IOP within 10
communications error.
the Array Point
R688