BACnet communication BinaryInput
■BACnet communication BinaryInput (Un\G9080 to Un\G9384)
This buffer memory area is used for the BinaryInput object.
Address
Un\G9080 to Un\G9084
Un\G9100 to Un\G9104
Un\G9120 to Un\G9124
Un\G9140 to Un\G9144
Un\G9160 to Un\G9164
Un\G9180 to Un\G9184
Un\G9200 to Un\G9204
Un\G9220 to Un\G9224
Un\G9240 to Un\G9244
Un\G9260 to Un\G9264
Un\G9280 to Un\G9284
Un\G9300 to Un\G9304
Un\G9320 to Un\G9324
Un\G9340 to Un\G9344
Un\G9360 to Un\G9364
Un\G9380 to Un\G9384
When the value of `Module READY` (Un\G34, b0) was changed from 0 to 1, the BinaryInput object settings
are reflected. ( Page 57 BinaryInput object setting)
The following table lists the buffer memory area format (BACnet communication BinaryInput 1) of the BinaryInput object.
Address
Name
Un\G9080,
Object ID
Un\G9081
Un\G9082
PresentValue
Un\G9083
OutOfService
Un\G9084
Reliability
*1 Stores the setting value of BinaryInput object setting No.1.
APPX
90
Appendix 1 Buffer Memory
Description
BACnet communication BinaryInput 1
BACnet communication BinaryInput 2
BACnet communication BinaryInput 3
BACnet communication BinaryInput 4
BACnet communication BinaryInput 5
BACnet communication BinaryInput 6
BACnet communication BinaryInput 7
BACnet communication BinaryInput 8
BACnet communication BinaryInput 9
BACnet communication BinaryInput 10
BACnet communication BinaryInput 11
BACnet communication BinaryInput 12
BACnet communication BinaryInput 13
BACnet communication BinaryInput 14
BACnet communication BinaryInput 15
BACnet communication BinaryInput 16
Description
b0 to b9: Object type
Stores the object type. (Fixed at 3)
b10 to b31: Instance
Stores the instance number. (0 to 4194303)
number
b0: PresentValue
Stores the current binary value.
• ON: Active
• OFF: Inactive
b0: OutOfService
Sets the value of the OutOfService property.
• ON: TRUE
• OFF: FALSE
b0 to b5: Reliability
Stores the value of the Reliability property.
• 0: NoFaultDetected
• 1: NoSensor
• 2: OverRange
• 3: UnderRange
• 4: OpenLoop
• 5: ShortedLoop
• 6: NoOutput
• 7: UnreliableOther
• 8: ProcessError
• 9: MultiStateFault
• 10: ConfigurationError
*1