BACnet communication BinaryValue
■BACnet communication BinaryValue (Un\G9720 to Un\G10028)
This buffer memory area is used for the BinaryValue object.
Address
Un\G9720 to Un\G9728
Un\G9740 to Un\G9748
Un\G9760 to Un\G9768
Un\G9780 to Un\G9788
Un\G9800 to Un\G9808
Un\G9820 to Un\G9828
Un\G9840 to Un\G9848
Un\G9860 to Un\G9868
Un\G9880 to Un\G9888
Un\G9900 to Un\G9908
Un\G9920 to Un\G9928
Un\G9940 to Un\G9948
Un\G9960 to Un\G9968
Un\G9980 to Un\G9988
Un\G10000 to Un\G10008
Un\G10020 to Un\G10028
When the value of `Module READY` (Un\G34, b0) was changed from 0 to 1, the BinaryValue object settings
are reflected. ( Page 59 BinaryValue object setting)
The following table lists the buffer memory area format (BACnet communication BinaryValue 1) of the BinaryValue object.
Address
Name
Un\G9720,
Object ID
Un\G9721
Un\G9722
PresentValue
Un\G9723
OutOfService
Un\G9724
Reliability
Un\G9725
Value setting value
Un\G9726
Write setting
Un\G9727
Write control
Un\G9728
Update counter
Description
BACnet communication BinaryValue 1
BACnet communication BinaryValue 2
BACnet communication BinaryValue 3
BACnet communication BinaryValue 4
BACnet communication BinaryValue 5
BACnet communication BinaryValue 6
BACnet communication BinaryValue 7
BACnet communication BinaryValue 8
BACnet communication BinaryValue 9
BACnet communication BinaryValue 10
BACnet communication BinaryValue 11
BACnet communication BinaryValue 12
BACnet communication BinaryValue 13
BACnet communication BinaryValue 14
BACnet communication BinaryValue 15
BACnet communication BinaryValue 16
Description
b0 to b9: Object type
Stores the object type. (Fixed at 4)
b10 to b31: Instance
Stores the instance number. (0 to 4194303)
number
b0: PresentValue
Stores the current binary value.
• ON: Active
• OFF: Inactive
b0: OutOfService
Sets the value of the OutOfService property.
• ON: TRUE
• OFF: FALSE
b0 to b5: Reliability
Stores the value of the Reliability property.
• 0: NoFaultDetected
• 1: NoSensor
• 2: OverRange
• 3: UnderRange
• 4: OpenLoop
• 5: ShortedLoop
• 6: NoOutput
• 7: UnreliableOther
• 8: ProcessError
• 9: MultiStateFault
• 10: ConfigurationError
b0: PresentValue
Sets the binary value to be written to PriorityArray.
b0: Null setting flag
Sets whether or not to write Null to PriorityArray.
• ON: Write
• OFF: Do not write
b1 to 5: Priority
Sets the priority for writing to PriorityArray. (1 to 16)
b0: Write flag
Sets whether or not to write the Value setting value to PriorityArray.
The write flag is enabled when OutOfService is set to OFF (FALSE).
• ON: Write
• OFF: Do not write
Stores the number of times PresentValue was updated. (0 to 32767)
*1
*2
APPX
Appendix 1 Buffer Memory
A
93