Mitsubishi Electric MELSEC iQ-F Series User Manual page 26

Programmable controller
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Object
AnalogOutput
BinaryOutput
Multi-State Output
Any
4 FUNCTIONS
24
4.2 BACnet Object Function
Value setting value
Priority setting
value
Normal 32-bit floating-
1 to 16
point data
-0, subnormal number,
NaN (not a number), or

0 or 1
1 to NumberOfStates
Out of the range of 1 to
NumberOfStates
Any
0 or 17 or more
Null setting flag
Operation
OFF
Sets the Value setting value to the Priority
setting value position of PriorityArray.
ON
Sets Null to the Priority setting value position of
PriorityArray.
OFF
Reflects the value to the current value as it is.
ON
Sets Null to the Priority setting value position of
PriorityArray.
OFF
Sets the Value setting value to the Priority
setting value position of PriorityArray.
ON
Sets Null to the Priority setting value position of
PriorityArray.
OFF
Sets the Value setting value to the Priority
setting value position of PriorityArray.
ON
Sets Null to the Priority setting value position of
PriorityArray.
OFF
Error
(Setting value out of range error)
ON
Sets Null to the Priority setting value position of
PriorityArray.
Any
Error
(Setting value out of range error)