Mitsubishi Electric MELSEC iQ-F Series User Manual page 61

Programmable controller
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

■BinaryValue object setting
Item
Instance No.
Object Name
Inactive_Text
Active_Text
Minimum_Off_Time
Minimum_On_Time
Relinquish_Default
Description
Set an instance number for the BinaryValue object. (The same
value cannot be set in the BinaryValue object.)
Set an object name for the BinaryValue object. (The same value
cannot be set in a module.)
Set the text to be displayed at Inactive.
Set the text to be displayed at Active.
Set the minimum time that PresentValue remains Inactive.
Set the minimum time that PresentValue remains Active.
Set the value that will be set when PriorityArray is all NULL.
Setting range
0 to 4194303
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
0 to 4294967295
(Default: 0)
0 to 4294967295
(Default: 0)
• Inactive
• Active
(Default: Inactive)
6 PARAMETER SETTINGS
6.3 Basic Settings
6
59

Advertisement

Table of Contents
loading