BACnet communication BinaryOutput
■BACnet communication BinaryOutput (Un\G9400 to Un\G9709)
This buffer memory area is used for the BinaryOutput object.
Address
Un\G9400 to Un\G9409
Un\G9420 to Un\G9429
Un\G9440 to Un\G9449
Un\G9460 to Un\G9469
Un\G9480 to Un\G9489
Un\G9500 to Un\G9509
Un\G9520 to Un\G9529
Un\G9540 to Un\G9549
Un\G9560 to Un\G9569
Un\G9580 to Un\G9589
Un\G9600 to Un\G9609
Un\G9620 to Un\G9629
Un\G9640 to Un\G9649
Un\G9660 to Un\G9669
Un\G9680 to Un\G9689
Un\G9700 to Un\G9709
When the value of `Module READY` (Un\G34, b0) was changed from 0 to 1, the BinaryOutput object settings
are reflected. ( Page 58 BinaryOutput object setting)
The following table lists the buffer memory area format (BACnet communication BinaryOutput 1) of the BinaryOutput object.
Address
Name
Un\G9400,
Object ID
Un\G9401
Un\G9402
PresentValue
Un\G9403
OutOfService
Un\G9404
Reliability
Un\G9405
Update counter
Un\G9406
Value setting value
Un\G9407
Write control
Un\G9408
Update counter
Description
BACnet communication BinaryOutput 1
BACnet communication BinaryOutput 2
BACnet communication BinaryOutput 3
BACnet communication BinaryOutput 4
BACnet communication BinaryOutput 5
BACnet communication BinaryOutput 6
BACnet communication BinaryOutput 7
BACnet communication BinaryOutput 8
BACnet communication BinaryOutput 9
BACnet communication BinaryOutput 10
BACnet communication BinaryOutput 11
BACnet communication BinaryOutput 12
BACnet communication BinaryOutput 13
BACnet communication BinaryOutput 14
BACnet communication BinaryOutput 15
BACnet communication BinaryOutput 16
Description
b0 to b9: Object type
Stores the object type. (Fixed at 4)
b10 to b31: Instance
Stores the instance number. (0 to 4194303)
number
b0: PresentValue
Stores the current binary value.
• ON: Active
• OFF: Inactive
b0: OutOfService
Sets the value of the OutOfService property.
• ON: TRUE
• OFF: FALSE
b0 to b5: Reliability
Stores the value of the Reliability property.
• 0: NoFaultDetected
• 1: NoSensor
• 2: OverRange
• 3: UnderRange
• 4: OpenLoop
• 5: ShortedLoop
• 6: NoOutput
• 7: UnreliableOther
• 8: ProcessError
• 9: MultiStateFault
• 10: ConfigurationError
b0: Null setting flag
Sets whether or not to write Null to PriorityArray.
• ON: Write
• OFF: Do not write
b1 to 5: Priority
Sets the priority for writing to PriorityArray. (1 to 16)
b0: PresentValue
Sets the binary value to be written to PriorityArray.
b0: Write flag
Sets whether or not to write the Value setting value to PriorityArray.
The write flag is enabled when OutOfService is set to OFF (FALSE).
• ON: Write
• OFF: Do not write
Stores the number of times PresentValue was updated. (0 to 32767)
*1
*2
APPX
Appendix 1 Buffer Memory
A
91