■AnalogInput object setting
Item
Instance No.
Object Name
Units (Select)
Units (Input)
■AnalogOutput object setting
Item
Instance No.
Object Name
Units (Select)
Units (Input)
Relinquish_Default
6 PARAMETER SETTINGS
56
6.3 Basic Settings
Description
Set an instance number for the AnalogInput object. (The same
value cannot be set in the AnalogInput object.)
Set an object name for the AnalogInput object. (The same value
cannot be set in a module.)
Set a unit. (The value can be set only when "Other" is selected in
the drop-down menu.)
Input a setting value when Units (Select) is set to "Other".
Description
Set an instance number for the AnalogOutput object. (The same
value cannot be set in the AnalogOutput object.)
Set an object name for the AnalogOutput object. (The same value
cannot be set in a module.)
Set a unit. (The value can be set only when "Other" is selected in
the drop-down menu.)
Input a setting value when Units (Select) is set to "Other".
Set the value that will be set when PriorityArray is all NULL.
Setting range
0 to 4194303
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
• 0: square-meters
• 1: square-feet
• 2: milliamperes
• 3: amperes
• 4: ohms
• 5: volts
• 6: kilovolts
• 7: megavolts
• 8: volt-amperes
• 9: kilovolt-amperes
• Others
(Default: 0: square-meters)
10 to 65535
(Default: Empty)
Setting range
0 to 4194303
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
• 0: square-meters
• 1: square-feet
• 2: milliamperes
• 3: amperes
• 4: ohms
• 5: volts
• 6: kilovolts
• 7: megavolts
• 8: volt-amperes
• 9: kilovolt-amperes
• Others
(Default: 0: square-meters)
10 to 65535
(Default: Empty)
32-bit floating point
-38
38
1.1810
to 3.410
(Default: 0)