Item
Active_Text
■BinaryOutput object setting
Item
Instance No.
Object Name
Polarity
Inactive_Text
Active_Text
Minimum_Off_Time
Minimum_On_Time
Relinquish_Default
6 PARAMETER SETTINGS
58
6.3 Basic Settings
Description
Set the text to be displayed at Active.
Description
Set an instance number for the BinaryOutput object. (The same
value cannot be set in the BinaryOutput object.)
Set an object name for the BinaryOutput object. (The same value
cannot be set in a module.)
Set a polarity.
Set the text to be displayed at Inactive.
Set the text to be displayed at Active.
Set the minimum time that PresentValue remains Inactive.
Set the minimum time that PresentValue remains Active.
Set the value that will be set when PriorityArray is all NULL.
Setting range
16 one-byte alphanumeric
characters maximum
(Default: Empty)
Setting range
0 to 4194303
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
• Positive polarity
• Negative polarity
(Default: Positive polarity)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
0 to 4294967295
(Default: 0)
0 to 4294967295
(Default: 0)
• Inactive
• Active
(Default: Inactive)