Siemens SIMATIC C7-613 Manual page 64

Table of Contents

Advertisement

Integration into the User Program
All 5 DBs are not always used for a language:
• If you do not need more than 64 screens, only a single SCREEN DB is created.
• If you do not need more than 64 messages, only a single MESSAGE DB is
created.
The configuration interface also assigns the DB numbers consecutively in these
cases (refer to Table 4-2).
This consecutive sequence of DBs may not be changed.
Table 4-2
DB Structure at a max. of 64 screens and max. of 64 messages
DB Number
n–1
n
Language 1:
n+1
n+2
n+3
Language 2:
n+4
n+5
n+6
Language 3:
n+7
n+8
n+9
Language 4:
n+10
n+11
n+12
Language 5:
n+13
n+14
n+15
4-8
Block name
Block ID
MENU
MENU
CONFIG
CFG
SCREEN
SCREEN
MESSAGE
MESSAG
INFO
INFO
SCREEN
SCREEN
MESSAGE
MESSAG
INFO
INFO
SCREEN
SCREEN
MESSAGE
MESSAG
INFO
INFO
SCREEN
SCREEN
MESSAGE
MESSAG
INFO
INFO
SCREEN
SCREEN
MESSAGE
MESSAG
INFO
INFO
Description
Contains the screen hierarchy
Configuration DB with the following
retentive data:
Last set language, character set,
date format, system language,
system message $002, contrast,
passwords, password level
Configuration data for ...
Process screens 0 to 63
Messages 0 to 63
Info texts 0 to 127
Configuration data for ...
Process screens 0 to 63
Messages 0 to 63
Info texts 0 to 127
Configuration data for ...
Process screens 0 to 63
Messages 0 to 63
Info texts 0 to 127
Configuration data for ...
Process screens 0 to 63
Messages 0 to 63
Info texts 0 to 127
Configuration data for ...
Process screens 0 to 63
Messages 0 to 63
Info texts 0 to 127
C7-613 Control System
A5E00138934-03

Hide quick links:

Advertisement

Table of Contents
loading