Siemens SIMATIC C7-613 Manual page 165

Table of Contents

Advertisement

Error Code
(W#16#...)
880A
880B
C7-613 Control System
A5E00138934-03
Error Information for HMI FBs and System Messages
Cause
A selected process
screen/special screen or an info
text is not available.
A screen was selected in the
screen number range 128 to 255,
but the screen is not a special
screen.
The selected process
screen/special screen cannot be
shown at the present time with
control job 51 (display image
selection).
Remedy
Check whether a configuration is
available for the selected object. A
process screen or info text is configured
if at least one character is edited in the
static text.
Only the numbers 1 to 127 are valid for
the selection of process screens. In the
range of 128 to 255 only the screen
numbers of special screens (see Section
4.5.3) can be selected.
A process screen/special screen cannot
be selected, if an object with a higher
display priority (refer to Section 5.8) is
currently being displayed.
Repeat the control job when the higher
priority object is no longer displayed.
Use the "OBJ_TYPE" parameter on the
"HMI API" FB to obtain the type of the
object that is currently being displayed
(refer to Section 4.5).