Digital outputs
Note
Technological functions utilize fast digital outputs. These outputs must only be
connected to resistive loads.
Number
Number of outputs
•
Of those are high-speed outputs
Cable length
•
Unshielded
•
Shielded
Voltage, currents, potentials
Rated load voltage L+
•
Polarity reversal protection
Accumulated output current
(per group)
•
Vertical mounting position
– Up to 40°C
– Up to 50°C
•
45 ° mounting position
– Up to 45°C
•
Horizontal mounting position
– Up to 40°C
Galvanic isolation
•
Between channels and P-bus
•
Between channels
– In groups of
Permissible potential difference
•
Between different circuits
Insulation tested at
Current consumption from load voltage L+
C7-613 Control System
A5E00138934-03
16
4
Maximum 600 m
Maximum 1,000 m (109 yd.)
24 VDC
Yes
Max. 3.0 A
Max. 2.0 A
Max. 2.0 A
Max. 2.0 A
Yes
Yes
8
75 VDC/60 VAC
500 V DC
Max. 20 mA per group
Technical data