Data for selecting an actuator
Output range (rated values)
•
Voltage
•
Current
Load resistance
(in the rated range of the output)
•
Voltage outputs
– ohmic load
– Capacitive load
•
Current outputs
– ohmic load
– inductive load
Voltage output
•
Short-circuit protection
•
Short-circuit current
Current output
•
No-load voltage
Destruction limit for externally applied
voltages / currents
•
Output voltage to M
ANA
•
Current
Connection of actuators
•
For voltage output
– 2-wire connection
– 4-wire connection (measuring line)
•
For current output
– 2-wire connection
A-20
±10 V
0 V to 10 V
±20 mA
0 mA to 20 mA
4 mA to 20 mA
Minimum 1 kΩ
Maximum 0.1 μF
Maximum 300 Ω
max. 0.1 mH
Yes
55 mA, typically
Typically 17 V
Maximum 16 V continuous;
Max. 50 mA continuous
Possible, without cable resistance compensation
Not possible
Possible
C7-613 Control System
A5E00138934-03