Error Code
(W#16#...)
8102
8103
8211
8212
8213
8214
8215
8221
8222
C7-613 Control System
A5E00138934-03
Error Information for HMI FBs and System Messages
Cause
Parameter 2 ("JOB_PAR2") of the
job compartment has an invalid
value for this job.
Parameter 3 ("JOB_PAR3") of the
job compartment has an invalid
value for this job.
The number of one of the data
blocks for the configuration data
is incorrectly specified in the
"ADDINFO" parameter, or the DB
is not available.
The DB specified in the
"ADDINFO" parameter is too
short.
The DB specified in the
"ADDINFO" parameter does not
have the "unlinked" attribute.
The DB specified in the
"ADDINFO" parameter is
write-protected.
The ID of DB specified in the
"ADDINFO" parameter is invalid.
The number of the event DB
specified in the "EVENT_DB"
parameter is incorrect, or the DB
is not available.
This check is performed only
after a backup job is initiated.
The DB for backing up the event
buffer on the MMC that is
specified in the "EVENT_DB"
parameter is too short.
This check is performed only
after a backup job is initiated.
Remedy
Valid values for this job can be found in
the description of the controller tasks
(refer to Section 4.5.3).
Valid values for this job can be found in
the description of the controller tasks
(refer to Section 4.5.3).
Check to determine whether the
specified DB number is a valid DB
number for this CPU.
Check to determine whether the
specified data block is loaded.
Correct the DB number or create the
configuration again (refer to Section 4.3).
Check to determine whether the
specified DB (DB number in
hexadecimal form) is the correct DB or
check the structure of the specified DB.
Information on the DB structure is
contained in Appendix C.1 to C.5.
Check to determine at the specified DB
(DB number in hexadecimal form)
whether the "unlinked" attribute is set. To
select the "unlinked" attribute, refer to
the STEP 7 Online Help.
Remove the write protection from the
specified DB (DB number in
hexadecimal form). For information on
removing the write protection, refer to
the STEP 7 Online Help.
Check the block ID of the specified DB
(DB number in hexadecimal form).
Information on the block ID is contained
in Appendix C.1 to C.5.
Check to determine whether the
specified DB number is a valid DB
number for this CPU.
Check to determine whether the
specified block is loaded.
Correct the DB number, or create the
corresponding EVENT_DB (refer to
Section 4.6.2).
Check to determine whether the
specified DB is the correct DB or check
the length (6144 bytes) and the structure
of the specified DB. Information on the
DB structure is contained in
Section 4.6.2 .