Safety
Standard references
Protection against ingress of
solid foreign bodies and water
•
Front panel
•
Housing
Electromagnetic compatibility (EMC)
Emitted interference
Limit class
Cable-fed disturbances on DC
supply cables
Noise immunity on signal cables
Interference immunity from static
discharges
Radio frequency-proof
Climatic conditions
Temperature
•
Operation
•
Storage/transport
Relative humidity
•
Operation
•
Storage/transport
Air pressure
•
Operation
•
Storage/transport
A-2
DIN EN 61131-2 corresponds to IEC 61131-2
IP65, to IEC 60529, NEMA 4X
IP20, to IEC 60529
A
in accordance with EN55011
±2 kV (to IEC 61000-4-4; burst)
Surge measurements with additional protective elements:
±1 kV (in accordance with IEC 61000-4-5; μs-pulse/cable to cable)
±2 kV (in accordance with IEC 61000-4-5; μs-pulse/cable to ground)
±2 kV (to IEC 61000-4-4; burst)
±6 kV, contact discharge
ESD)
±8 kV, air discharge
ESD)
10 V/m,
with 80% amplitude modulation at 1 kHz,
10 kHz to 80 MHz (in accordance with IEC 61000-4-6)
10 V/m,
with 80% amplitude modulation at 1 kHz,
80 kHz to 1 GHz (in accordance with IEC 61000-4-3)
10 V/m,
pulse-modulated 50 % ED at 900 MHz and
1.89 GHz (in accordance with IEC61000-4-3)
Tested in accordance with IEC 60068-2-1 and IEC 60068-2-2:
0 °C to +40 °C
for horizontal mounting
0 °C to +45 °C
for 45 ° mounting
0 °C to +50 °C
for vertical mounting
Note:
•
When the device is in a horizontal mounting position, display
readability is limited.
•
At temperatures < 10 °C, rapidly changing displays do not appear
correctly.
-20 °C to +70 °C
Tested in accordance with IEC 60068-2-3
5% to 95% at 25 °C (no condensation)
5% to 95% at 25 °C (no condensation)
1080 to 795 hPa (corresponds with -1000 m to +2000 m)
1080 to 660 hPa (corresponds with -1000 m to +3500 m)
(in accordance with IEC 61000-4-2;
(in accordance with IEC 61000-4-2;
C7-613 Control System
A5E00138934-03