Status, interrupts, diagnostics
Interrupts
Diagnostic functions
Data for selecting an encoder for standard DIs
Input voltage
Rated value
For signal "1"
For signal "0"
Input current
For signal "1"
Delay of the standard inputs
Configurable
Rated value
Input delay when using technological
functions
Input characteristic
Connection of 2-wire BEROs
Permissible quiescent current
A-12
Yes, if the corresponding channel is configured as an
interrupt input
For application of technological functions, refer to
"S7-300 Programmable Controllers CPU31xC
Technological Functions" manual.
No diagnostics when operated as standard I/O
When using the technological functions, cf. S7-300
Programmable Controller, CPU31xC Technological
Functions" manual
24 VDC
15 V to 30 V
-3 V to 5 V
7 mA, typically
Yes (0.1/0.5/3/15 ms)
3 ms
16 μs
In accordance with IEC 1131, Type 1
Possible
Max. 1.5 mA
C7-613 Control System