Encoder selection data
Input ranges (rated values)/input resistance
Voltage
Current
Resistance
Resistive thermometer
Permissible input voltage
(destruction limit)
For voltage input
For current input
Permissible input current (destruction limit)
For voltage input
For current input
Connection of signal encoders
for voltage measurement
For current measurement
– As 2-wire measuring transducer
– As 4-wire measuring transducer
For measuring resistance
– With 2-wire connection
– With 3-wire connection
– With 4-wire connection
Linearization of characteristic curve
For resistive thermometer
Temperature compensation
Technical unit for temperature measurement Degrees Centigrade/Fahrenheit/Kelvin
C7-613 Control System
A5E00138934-03
±10 V/100 kΩ
0 V to 10 V/100 kΩ
±20 mA / 50 Ω
0 mA to 20 mA/50 Ω
4 mA to 20 mA/50 Ω
0 Ω to 600 Ω/10 MΩ
Pt 100/10 MΩ
Maximum 30 V continuous;
Maximum 2.5 V continuous;
Max. 0.5 mA continuous
Max. 50 mA continuous
Possible
Possible, with external power supply
Possible
Possible, without cable resistance compensation
Not possible
Not possible
By software
Pt 100
No
Technical data
A-17