Optional: Normal range indication option

Procedure
1. Modify each of the stickers to desired size prior to proceeding to step
Step
The stickers are intended to be installed on the dial only and should
not be applied on the inside or outside of the housing cover.
2. Remove housing cover.
3. Slide ON/OFF switch to the OFF position and wait for LED to stop
flashing.
4. Gently move the needle in the clockwise direction until it is pointing
at the Red X.
Note
Use caution as the electronics assembly is connected to the needle.
5. Remove any debris on the dial, so it does not become trapped under
the sticker.
6. Peel back the white paper backing of the sticker.
7. Slowly lower the sticker onto the surface of the dial in the desired
location and rub it in place firmly. Repeat steps 6 and 7 until desired
indication locations are set.
8. Slide ON/OFF switch to the ON position.
9. Replace housing cover.
Quick Start Guide
2.
Stickers should be applied in an environment where the ambient
temperature is above 50 °F (10 °C).
Moving the sticker after initial contact is not recommended as
this decreases the amount of adhesive on the back of the sticker.