Setting "YES" this Zone will use the programmed HI-LOW sensitivity Groups ( refer to HIGH AND LOW
SENSITIVITY GROUPS above) to switch to LOW sensitivity during DAY and to HIGH sensitivity during
the Night .
Prealarm enable: YES/NO.
This feature enables viewing and managing pre-alarm for sensors assigned to the zone
Alarm Correlation - Indicates the number of alarm devices assigned to the zone to activate the siren
outputs associated with this zone.
Example:
Zone 1 Alarm Correlation = 3
and in the "Utilities / Parameters / Specials / Sirens" menus you have programmed
the entry "Active sirens on correlation" = SI
you will have to activate at least 3 Zone 1 devices to activate the siren output and all programmed SND
type modules associated with this zone.
AM_8200
Programming Manual
PAGE - 43
AM82000_manu-prog-ENG
Doc. M-162.1-AM8200-ENG Rev A2