Master Programming Level
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM

3=ZONE SETUP

Programming Screen #2
ZONE SETUP

1=ENABLE

2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
MS-9200UDLS PN 52750:A 11/04/05
3.6.3 Zone Setup
Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as
illustrated below:
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
1=ZONE TYPES
2=ZONES AVAILABLE
3.6.3.1 Enable
Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the
following screen:
ZONE TO ENABLE
Z
This screens allows the programmer to enable zones, one at a time. A flashing
cursor appears next to the Z, prompting the programmer to enter a two digit zone
number (01 - 99). When the second digit is entered, the zone will be enabled and
the cursor returns to the original position next to the Z. Another zone can then be
enabled.
ZONE SETUP
ZONE SETUP
Zone Setup Screen #2
ZONE SETUP
Zone Setup Screen #3
Enable Screen
Programming
75