At the end of the Auto-programming procedure a summary of the devices found on the line is displayed
Where:
TYPE = Type of devices found ( see table above)
ew device found
NEW = N
NFO = Devices previously programmed but not coherent with what was detected during the Auto-Learn procedure
TOT
= total of devices detected on the line ( NEW + NFO + correctly programmed devices.)
MIS = Devices previously programmed but not detected during the Auto-Learn
The SAVE control saves the devices detected during the Self-Learn according to the following mode:
- NEW and NFO are initialized through the default data.
- MIS are removed
- The correctly programmed devices keep the current programming
The data relevant to the initialized devices can be subsequently changed by entering the point programming
procedure.
The PROT ( Protocol ) control can display the table of devices for one of the two possible protocols: CLIP or ADV
Sample screen for CLIP detectors.
Important Note:
On Each Line, can be installed
a max number of 30 devices using CLIP
protocol.
PAGE - 34
NOTIFIER ITALIA
Programming Manual
Doc. M-162.1-AM8200-ENG Rev A2
AM_8200
AM8200_manu-prog-ENG