If the DEL equation duration time is not specified, the equation will be active until the reset of the
elements in the equation.
The maximum value of the duration time is 10 minutes
The maximum values of the delay time is 10 minutes.
The "SEDEL" operator is equal to the "DEL" operator, with the difference that, if during the delay time the
equation is not true any longer, the timer continues to count and then it activates the output device.
To re-set this timer perform an alarm or Fault reset.
is the operator that allows to program output activations at periodic time intervals.
There can be two formats :
FORMAT Type 1 : TIM (SU MO TU WE TR FR SA
Where : 00 = hours, MM = minutes
This format allows to perform programmings weekly, for specific days of the week
FORMAT Type 2 : TIM (MM GG AA
Activation date
(optional)
Where : MM = month, GG = day, AA =year
This format allows to perform programmings yearly
Example: IF the G90 software group equation is : TIM (SA SU 07.30 13.59)
THEN the G90 group will be active on Saturday and Sunday from 07.30 a.m. to 13.59.
N.B.:
If the day, month or year is not specified, the value assumes the meaning of "All days".
To not specify anything enter two signs "  " refer to the following example:
The start time and end time values, use the 24 hour format (midnight = 00.00 ... 23.59)
The value "00.MM" of end time MUST be higher than the value of the start time.
The maximum value for start time and end time is 23:59
PAGE - 68
NOTIFIER ITALIA
SDEL
TIM
Enter a
space character
activation days
(optional)
Enter a space
character
OO.MM
start time
TIM (   07.30 13.59)
Programming Manual
Doc. M-162.1-AM8200-ENG Rev A2
Enter a
space character
00.MM
00.MM)
start time
end time
Enter a space
character
OO.MM)
end time
AM_8200
AM8200_manu-prog-ENG