Example 2: A CMX-10RME (10 OUTPUT) card with address 10 will be programmed.
CMX-10RME – Hardware Address = 10
1 ª Output
2 ª Output
3 ª Output
4 ª Output
5 ª Output
6 ª Output
7 ª Output
8 ª Output
9 ª Output
10 ª Output
Example 3: a WSS-PR-I02 optical/acoustic device with address 2 will be programmed
WSS-PR-I02 - Address 2
Sounder
Flash
HARDWARE
TYPE-: An identifier identifying the model of the device (both for sensors and for modules)
SOFTWARE
TYPE: An identifier identifying the type of device behavior.
It can assume different meanings depending on the model or device type-hardware.
It may indicate device behavior (eg "activates for each fault")
Or it can indicate the type of cabling (eg double balancing, free contact output, etc.)
ZONES: are set of points in same physical area
Used as basic indications as stated in EN 54.2 to identify the position of an event.
500 physical zones in stand alone or in 16 loop network configuration.
2000 physical zones in128 loop network configuration
A maximum of 32 points can be associated to each zone.
GROUPS: A group is a software set of devices that can be used to program associations between Inputs and
Outputs and perform actions triggered by input or alarm events.
400 groups in 16 loop network configuration.
1600 groups in 128 loop network configuration
Groups have no limit in number of points.
AM_8200
AM82000_manu-prog-ENG
SUB-ADDRESS 1
SUB-ADDRESS 2
SUB-ADDRESS 3
SUB-ADDRESS 4
SUB-ADDRESS 5
SUB-ADDRESS 6
SUB-ADDRESS 7
SUB-ADDRESS 8
SUB-ADDRESS 9
SUB-ADDRESS 10
SUB-ADDRESS = 1
SUB-ADDRESS = 2
Programming Manual
Doc. M-162.1-AM8200-ENG Rev A2
SUB-address in Panel
10.1
10.2
10.3
10.4
10.5
10.6
10.7
10.8
10.9
10.10
SUB-address in Panel
2.1
2.2
PAGE - 3