INPUT MODULES

CONNECTION TYPE

PAGE - 36
NOTIFIER ITALIA

Summary of SW Type-ID for modules

SW Type_ID
MON3
Input module
Input module used for N.O. contacts
(Connection in conformity with EN54 rule).
MON
Input module used for N.O. contacts or any device
Not compliant to EN 54
MMX-2 input module (obsolete module)
Input module used for 4- wire conventional smoke detectors
SCON
not detected during the self-programming.
N.B.: this type has a reset time which is longer than the modules
programmed as "MONITOR"
It is valid for the M710E-CZ and M710E-CZR module for the connection of
conventional sensors
SCO2
It is automatically detected during the self-programming
Input module
Input module used to interface with N.O. contact, with alarm when
NONA
It is closed. The activation of a "NONA" type module, does not generate an
Alarm condition, that is:
- the alarm LED is not on
- "APND" or "GPND" type modules do not activate. Only output modules
coupled
to CBE are activated
Input module used like the NONA device, but each state change is activated
by the buzzer, for one second.
STAT
PULL
Same as MON3; in addition, the" MANUAL BUTTON" reading appears
GTW
AGILE WIRELESS GATEWAY
Input module used to check the N.C. inputs
When the line is off, an alarm is indicated
NCMN
In case of line short circuit, a FAULTis indicated
Programming Manual
Doc. M-162.1-AM8200-ENG Rev A2
TYPE OF DEVICE
NRXI-GATE
AM8200_manu-prog-ENG
AM_8200