Possible Hart Error Messages - ABB TTF200 Operating Instruction

Field-mount temperature transmitter
Hide thumbs Also See for TTF200:
Table of Contents

Advertisement

30
TTF200 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A
9.1

Possible HART error messages

Range
Displays
the
device
status
Electronics
F
Electronics
S
Electronics
F
Electronics
M
Electronics
F
Electronics
I
Installation /
I
Configuration
Electronics
I
Electronics
F
Electronics
F
Electronics
F
Installation /
C
Configuration
Sensor
F
Sensor
F
Sensor
F
Sensor
F
Sensor
F
Installation /
I
Configuration
Installation /
I
Configuration
Installation /
F
Configuration
Installation /
C
Configuration
Operating conditions
F
Installation /
I
Configuration
Installation /
C
Configuration
Operating conditions
S
NOTICE
If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
Change from one to two columns
Displays
Cause
the DIAG.
NO.
1
Device defective
2
Ambient temperature overshot /
undershot
3
EEPROM defective
4
Electronics overload
5
Memory error
7
LCD display connected
8
Device write-protected
9
EEPROM busy
12
Sensor input defective (communication)
13
Sensor input defective (error)
14
Sensor input defective (ADC error)
32
Diagnostics simulation mode
34
Measuring error, sensor
35
Short-circuit, sensor
36
Wire break, sensor
37
Range overshot, sensor
38
Range undershot, sensor
41
Single-point adjustment active, sensor
42
Two-point adjustment active, sensor
65
Configuration defective
71
Reconfiguration is running
72
Error in the application
74
Analog output adjustment active
75
Analog output in simulation
76
Values overshot
Remedy
Replace the device
Check environment; reposition measuring
point if required
Replace the device
Factory reset
Factory reset
Status info; not an error
Status info; not an error
Status info; not an error
Replace the device
Replace the device
Replace the device
Not an error, diagnostic info, measurement
OK
Check sensor connection
Check sensor connection
Check sensor connection
Check measuring limits
Check measuring limits
Status info; not an error
Status info; not an error
Check configuration:
A) Wrong device
B) Span is too small
C) Incorrect configuration data
Status info; not an error
Check configuration, connections; reset to
factory settings
Status info; not an error
Status info; not an error
Check parameters:
A) Sensor limits overshot
B) Span is too small