Connectivity Interface - ABB TLE 625 Series Installation Manual

Table of Contents

Advertisement

65/72
5

Connectivity interface

J35µP - RS232
Connectivity rack
TLE Series 625 & 750
J35µP - RS232
Connectivity rack
TLE Series 1000
Fig. 5-1 TLE Series 625 to 1000 - Connectivity rack and Serial port J35µP – RS232
TLE Series 625 to 1000 has the following equipment's:
Serial Port J35µP - RS232 (see Section 5.1).
Customer Interface board (see Section 5.2).
Connectivity rack ready for the installation of four connectivity boards.
Possible connectivity configurations with TLE Series 625 to 1000
9
8
6
7
5
3
4
2
1
20
18
19
17
15
16
14
12
13
Fig. 9-2 Connectivity Slots
Note!
The installation of any option board must be performed only by an ABB Service Technician.
Prior to the installation, connection and cabling of any option board the UPS must be completely
powered down and all the power sources that will be connected to the option board must be de-
energized.
Option board shall be connected only to Safety Extra Low Voltage circuits (SELV for IEC-UL-
CSA60950-1): voltage up to 30Vac / 42.4Vpk or 60Vdc maximum and galvanically separated from
AC Mains supply.
Keep SELV cables separated from high voltage cables.
Q1
J2
J3
J5
2
1
11
10
21
22
J4
TLE Series 625 to 1000 PurePulse™ UL S2
Q1
Connectivity rack
For a Single UPS it's possible to install the following
connectivity boards:
max. 3 "Customer Interface" boards;
-
- max. 2 "3-ph SNMP/WEB Plug-in Adapter" boards.
For a Parallel System (max. 6 UPS) it's possible to install
the following connectivity boards:
max. 3 "Customer Interface" boards for each UPS;
-
- max. 2 "3-ph SNMP/WEB Plug-in Adapter" boards for
RPA Parallel System.
UPS Installation Guide / REV-B