47/54
5

Connectivity interface

Fig. 5-1 MegaFlex 1000 to 1600 - Connectivity rack and Serial port J35µP – RS232 / J35DSP – RS232
MegaFlex 1000 to 1600 has the following equipment's:
Serial Port J35µP - RS232 (see Section 5.1).
Serial Port J35DSP - RS232 (only for ABB Service Center).
Customer Interface board (see Section 5.2).
Connectivity rack ready for the installation of four connectivity boards.
XA terminal block (see Section 4.11).
Possible connectivity configurations with MegaFlex 1000 to 1600
5
4
2
3
1
15
16
14
12
13
Fig. 5-2 Connectivity Slots
Note!
The installation of any option board must be performed only by an ABB Service Technician.
Prior to the installation, connection and cabling of any option board the UPS must be completely
powered down and all the power sources that will be connected to the option board must be de-
energized.
Option board shall be connected only to Safety Extra Low Voltage circuits (SELV for IEC-UL-
CSA60950-1): voltage up to 30Vac / 42.4Vpk or 60Vdc maximum and galvanically separated from
AC Mains supply.
Keep SELV cables separated from high voltage cables.
J35DSP - RS232
XA
J35
µ
P - RS232
Connectivity rack
J2
J3
J5
2
1
10
11
9
8
6
7
22
21
19
20
18
17
J4
MegaFlex 1000 to 1600
For a Single UPS it's possible to install the following
connectivity boards:
max. 3 "Customer Interface" boards;
-
- max. 2 "3-ph SNMP/WEB Plug-in Adapter" boards.
For a Parallel System (max. 6 UPS) it's possible to install
the following connectivity boards:
max. 3 "Customer Interface" boards for each UPS;
-
- max. 2 "3-ph SNMP/WEB Plug-in Adapter" boards for
RPA Parallel System.
UPS Installation Guide / REV-A
J35
DSP
J35
µ
P
Customer
Interface
Connectivity
XA
SNMP
rack