4.9.3 TLE Series 1000 - Power connection with Common Input Utility

Power connection cables are connected to bus bars using M12 bolts.
The bolts of the connection cables must be tightened with a torque wrench at 530 Lb-in / 60 Nm.
Common Input Utility - Rectifier / Bypass
L1-1
Rectifier + Bypass Phase A (L1)
L2-1
Rectifier + Bypass Phase B (L2)
L3-1
Rectifier + Bypass Phase C (L3)
Note!
The interconnection links BR1, BR2 and BR3 must remain connected (see Fig. 4.9.3-1).
Output Load
L1
Load phase A (L1)
N
Neutral
External Battery connection
+
Positive pole of the Battery
-
Negative pole of the Battery
PE
Battery cabinet Ground
Bolt Size/Torque: M10 / 355 Lb-in - 40 Nm
Warning!
Before closing the "External Battery Fuses", verify for correct polarity of the Battery connection.
Note!
To meet standards concerning electromagnetic compliance, the connection between the UPS
and external Battery must be done by using a shielded cable or suitable shielded (steel)
conduit!
Interconnections links
BR1, BR2 and BR3
must remain connected
Q1
Fig. 4.9.3-1 TLE Series 1000 - Power connection Common Input Utility
L2
PE
TLE Series 625 to 1000 PurePulse™ UL S2
!
Rectifier
Load
L3
Load
L2
Load
L1
cables input from the top of the UPS (see Section 4.9)
Load phase B (L2)
Ground
Power Section cabinet
UPS Installation Guide / REV-B
1
Utility
Typical installation
using common NEMA
two hole lugs
BR3
N
L3-1
Utility Neutral
Load Neutral
BR2
L2-1
BR1
L1-1
Position of the bus bars for
N
PE
L3
Load phase C (L3)
+
_
Typical installation
using common NEMA
two hole lugs
PE
N
Utility Neutral
Load Neutral
Neutral
Ground
In/Out Section cabinet
PE