6

Connectivity

6.1

Interfacing

Each UPS cabinet is provided with the User Interface Board (UIB). The UIB contains communication ports which provide information
about the UPS (single units) or the UPS system (parallel system).
The user interface is composed of (see also the figure 12 at the end of this section):
Slot for optional Modem card
Slot for optional SNMP card
PC / laptop connection
Status LED's
Graphical display connection
Multidrop configuration
Multidrop connection
UPS inputs
12VDC source
UPS outputs, dry ports
Interlock Function
Multi-Cabinet Configuration
Parallel BUS connector
6.1.1

Smart Port JD1 on Each Cabinet (Serial RS 232 / D-Sub 9-pin / Male)

The SMART PORT JD1 located on the UIB (see figure 10 above, detail 9) RS-232 serial port that allows the UPS module to be connected
to an external computer. The connector is a standard D-Sub, 9-pin, male. When installed, the optional SMART PORT in conjunction with
the software WAVEMON, allows an external computer to monitor the mains voltage and the UPS status continuously.
In the event of any changes the computer terminal will display a message.
(For details see our Monitoring Package: WAVEMON)
Figure 11 below represents the standard RS-232 interface cable used to connect an external computer to the UPS.
24 Conceptpower DPA 500 480V UL │94-12-043275 A02
JD1 (RS232 9-pin D-Sub/female) or USB
1 red LED and 1 green LED
JR3 (RJ 45)
SW2 (DIP-SWITCH)
JR2 (RJ 45)
X3 (Phoenix terminals)
X3 5/6 (Phoenix terminals)
X2 (Phoenix terminals)
X1 1/2 (Phoenix terminals)
SW1-9 (DIP-SWITCH)
JD8 (Sub D25/female)
Interface Cable
(9-pin D-Sub male-to-female)
1
(TXD)
2
(RXD)
3
(gnd)
5
.
.
.
9
UPS JD1
Figure 11: Connector cable – RS-232 Serial Port with 9-Pin D-Sub connection
1
2
(RXD)
(TXD)
3
(gnd)
5
.
.
.
9
Computer
9-pin D-Sub