TLE Series 625 to 1000
Power connection bus bars configuration for the top cable entry or bottom cable entry
The configuration of the TLE Series 625 to 1000 is with top cable entry as standard (see Fig. 4.9-3).
It is possible to configure the bus bars with bottom cable entry (see Fig. 4.9-4).
Top entry cables
Utility input & Load output
Q1
TLE Series 625 & 750
Q1
TLE Series 1000
Fig. 4.9-3 TLE Series 625 to 1000 – Power connection configuration bus bars with top cable entry (standard)
Power connection cables are connected to bus bars using M12 bolts.
The bolts of the connection cables must be tightened with a torque wrench at 530 Lb-in / 60 Nm.
Q1
TLE Series 625 & 750
Q1
TLE Series 1000
Fig. 4.9-4 TLE Series 625 to 1000 - Power connection configuration bus bars with bottom cable entry