battery string abnormal SOC or not.
5.3.3 Cables Inspection:
[Periodical Maintenance] Visual inspect all the cables of battery system. Check the cables has
broken, aging, getting loose or not.
5.3.4 Balancing:
[Periodical Maintenance] The battery strings will become unbalance if long time not be full charged.
Solution: every 3 month should do the balancing maintenance (charge to full), normally it will been
done automatically by the communication between system and external device.
5.3.5 Output Relay Inspection:
[Periodical Maintenance] Under low load condition (low current), control the output relay OFF and
ON to hear the relay has click voice, that's mean this relay can off and on normally.
5.3.6 History Inspection:
[Periodical Maintenance] Analysis the history record to check has accident (alarm and protection)
or not, and analysis its reason.
5.3.7 Shutdown and Maintenance:
[Periodical Maintenance]
Some system function must be maintenance during the EMS restart, it is recommended to
maintenance the system every 6 months.
5.3.8 Recycle
NOTE
Damaged batteries may leak electrolyte or produce flammable gas.
In case a damaged battery needs recycling, it shall follow the local recycling regulation (i.e.
Regulation (EC) Nº 1013/2006 among European Union) to process, and using the best available
techniques to achieve a relevant recycling efficiency.