Pattern Operation - GE Fuji Electric AF-300ES Instructions Manual

1/2 - 350 horsepower
Table of Contents

Advertisement

LCD
GRAPHIC
FUNCTION
DISPLAY

PATTERN OPERATION

65
PATTERN
* 66
STAGE 1
* 67
STAGE 2
* 68
STAGE 3
* 69
STAGE 4
* 70
STAGE 5
* 71
STAGE 6
* 72
STAGE 7
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SETTING
DESCRIPTION
PATTERN OPERATION
A pattern operation can be set for seven
(7) individually set speeds (Function Codes
20 through 26) to run up to 6,000 seconds
each, forward or reverse direction (Function
Codes 66 through 72) with the following choice
of cycles:
0:
Inactive
1:
Single cycle
2:
Continuous cycle (repeating)
3:
Single cycle with continuous seventh speed
PATTERN STAGES
Each of the pattern operation's seven (7)
stages can be set based on the following
codes that includes direction of rotation,
selection of acceleration/deceleration
times (Function Codes 5, 6, 33 through 38),
and a maximum duration running time of 6,000
seconds each.
Code
FWD/REV
F1
FWD
F2
FWD
F3
FWD
F4
FWD
R1
REV
R2
REV
R3
REV
R4
REV
Example: Function Code 66 set at 15.00F2
15:00 -Run time is 15 seconds to
include accel rate.
F2 -Foward direction, ACC2/DEC2
timing set in Function Codes
33 and 34.
NOTES: –If a stage's timer is set at 0.00,
it will be skipped.
– /\ or \/ keys select the direction of
rotation, rate of acceleration and decel-
eration, and length of pattern stage run
time. The SHIFT >> key selects the digit of
the run time to be set using the /\ or \/ keys.
6-26
ACC/DECEL
ACC1/DEC1
ACC2/DEC2
ACC3/DEC3
ACC4/DEC4
ACC1/DEC1
ACC2/DEC2
ACC3/DEC3
ACC4/DEC4
FACTORY
SETTING
0
0.00S:F1
0.00S:F1
0.00S:F1
0.00S:F1
0.00S:F1
0.00S:F1
0.00S:F1
0.00S:F1
0.00S:F1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents