GE Fuji Electric AF-300ES Instructions Manual page 40

1/2 - 350 horsepower
Table of Contents

Advertisement

Table 5:
Terminal Identification/Function
Terminal
Terminal
Label
Name
L1, L2,
ac Supply Line
L3
Input Terminals
U, V, W
Drive Output
Terminals
P+, DB
External Braking
Resistor Terminals
N-, P+
External Braking
Unit Terminals
P+, P1
DC Reactor
E (G)
Ground Terminal
RO, TO
Control Power
Auxiliary Input
U1, U2
Auxiliary Transformer
Taps
Frequency Setting
11
Common Terminal
12
Frequency Setting
Voltage Input
13
Frequency Setting
Voltage Output Term.
C1
Frequency Setting
Current Input
V1
Voltage Input
Auxiliary Terminal
CM
Control Circuit
Common Terminal
FWD
Forward Command
Input Terminal
Reverse Command
REV
Input Terminal
BX
Motor Coast-To-Stop
Input Terminal
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Function
POWER TERMINAL BOARD
Connection for commercial power (200-230 VAC or 380-460 VAC);
3-phase; 50⁄60 Hz.
Connection for 3-phase induction motor.
Connection for external braking resistor.
(Only on 10 Hp or less.)
Connection for external braking resistor via external braking unit.
(Only required on 15 Hp)
Connection for a dc link reactor on unit rated 100 Hp and greater.
These terminals are jumpered on units rated 75 Hp and less.
Connection for ground. Note: Be sure to ground the chassis to
prevent electrical shock & to reduce radio noise.
Connection point for single-phase, 460 ac power for backing up the
control circuit power when input starter is used (40 Hp and greater.)
Factory connection set at U1 for 400 - 460 VAC input.
Reconnect to U2 for 380 VAC input. (40 Hp and greater)
CONTROL TERMINAL BOARD
Common terminal for terminals 12, 13, C1 & V1, and FMA (Do not
connect to CM terminal or electrical noise immunity may be lost.)
When 0 to +10 VDC (0 to 5V) is input, the maximum frequency is
reached at +10 VDC (5V) and is proportional to output frequency
down to 0 VDC. Input impedance is 22K ohm. Must be isolated source.
Regulated +10 VDC power supply for frequency setting potentiometer,
10mA or less (13 to terminal 11.)
When the input signal is +4 to +20mA dc, the maximum frequency is
reached at 20mA and is proportional down to a minimum frequency
setting at 4mA. Input impedance is 250 ohm. Must be isolated source.
Reaches maximum output frequency at +/- 10 VDC (the output
freq. is proportional down to 0 VDC.) Input impedance is 22K ohms.
Must be isolated source.
Common terminal for control input commands, and FMP pulse
output signal. (Do not connect to terminal 11.)
Forward command via FWD-CM (closed). Reverse command via
REV-CM (closed). When FWD-CM is closed and REV-CM is closed
at the same time, the drive will decelerate to stop.
Motor will coast-to-stop with BX-CM (closed). (For use when
applying mechanical brake with drive in operation.) Note: If
BX-CM is opened with FWD or REV closed, the drive will start
operating.
4-8