GE Fuji Electric AF-300ES Instructions Manual page 67

1/2 - 350 horsepower
Table of Contents

Advertisement

LCD
GRAPHIC
FUNCTION
DISPLAY
* 19
DC BRK t
MULTI STEP FREQUENCIES
Seven (7) digitally preset speeds can be programmed into Function Codes 20 through 26.
These can be used as part of a pattern operation (see Function Code 65) or individually selectable
through switching of control terminals X1, X2, and X3 (see Function Code 32.)
* 20
MULTI Hz-1
* 21
MULTI Hz-2
* 22
MULTI Hz-3
* 23
MULTI Hz-4
* 24
MULTI Hz-5
* 25
MULTI Hz-6
* 26
MULTI Hz-7
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SETTING
DESCRIPTION
DC INJECTION BRAKING TIME "ON"
The dc injection brake time is adjustable
from 0.1 to 30.0 seconds using this setting.
A setting of zero (0) causes dc braking to be
inactive.
Output
Frequency
Output
Voltage
Use care when applying dc braking as motor
CAUTION:
currents & temperatures can build up to very high levels in
a short period of time possibly resulting in motor damage.
MULTI STEP FREQUENCY #1
MULTI STEP FREQUENCY #2
MULTI STEP FREQUENCY #3
MULTI STEP FREQUENCY #4
MULTI STEP FREQUENCY #5
MULTI STEP FREQUENCY #6
MULTI STEP FREQUENCY #7
(Relationship between the terminals and multi-step frequency 1 to 7)
s
00
20
21
Multi-step
Analog
Speed
Speed
Frequency
Digital
1
2
X1 – CM
OFF
ON
OFF
X2 – CM
OFF
OFF
ON
X3 – CM
OFF
OFF
OFF
6-9
Brake
Time
22
23
24
25
26
Speed
Speed
Speed
Speed
Speed
3
4
5
6
7
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
ON
FACTORY
SETTING
0.0S
Brake Start
Frequency
Brake
Voltage
0.0
0.0
0.0
0.0
0.0
0.0
0.0