Accel/Decel Times - GE Fuji Electric AF-300ES Instructions Manual

1/2 - 350 horsepower
Table of Contents

Advertisement

LCD
GRAPHIC
FUNCTION
DISPLAY
32 (cont'd)

ACCEL/DECEL TIMES

* 33
ACC TIME 2
greater)
* 34
DEC TIME 2
greater)
* 35
ACC TIME 3
* 36
DEC TIME 3
* 37
ACC TIME 4
* 38
DEC TIME 4
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SETTING
DESCRIPTION
X5 - function selected by 4th digit:
- - - 0
ACC/DEC time selection (four steps
using X4 and X5)
- - - 1
Select motor #2 Function Codes
Function Code 03 to Function Code 39
Function Code 04 to Function Code 40
Function Code 07 to Function Code 41
Function Code 87 to Function Code 89
(This would ONLY be useful for
applications where a second motor
can be connected to the drive with
mechanical switchgear.)
- - - 2
Selects data protection mode (only
Function Code 95 can be changed)
X5 to CM contacts open - Protected (Change prevented)
X5 to CM contacts closed - Not Protected (Changeable)
- - - 3
Restart Function
NOTE: In order to bypass GE Safety software
(Er6), select "3" and install a wire jumper between
Terminal X5 and CM.
ACCELERATION TIME #2
Adjustable from 0.01 to 3600 seconds.
DECELERATION TIME #2
Adjustable from 0.01 to 3600 seconds.
NOTE: 100 Seconds for 40 Hp and greater.
Acceleration/Deceleration times 2 through 4
are identical in behavior to Function Codes
05 and 06 respectively. They can be activated
via the X4 and X5 terminals as explained for
Function Code 32 and the following chart.
Adjustable from 0.01 to 3600 seconds.
6-15
FACTORY
SETTING
10.0
(30Hp and less)
100
(40 Hp and
10.0
(30Hp and less)
100
(40 Hp and
15.0 (30Hp and less)
100 (40 Hp and greater)
15.0 (30Hp and less)
100 (40 Hp and greater)
3.0 (30Hp and less)
100 30 Hp and greater)
3.0 (30Hp and less)
100 (40 Hp and greater)