Table 12-1 RFI filter dimensions
Filter
Part
Applied Drive
No.
EFL-1.5 G9-4 6KE$243001X1B1
6KE$243002X1B1
EFL-4.0 G9-4 6KE$243003X1B1
6KE$243005X1B1
EFL-7.5 G9-4 6KE$243007X1B1
6KE$243010X1B1
EFL-15 G9-4 6KE$243015X1B1
6KE$243020X1B1
EFL-22 G9-4 6KE$243025X1B1
6KE$243030X1B1
Recommended Installation Instructions
It is necessary that to conform to EMC Directive, these
instructions must be followed. Follow the usual safety
procedures when working with electrical equipment. All
electrical connections to the filter, drive and motor must
be made by a qualified electrical technician. (Refer to
Figure 12-2 and Figure 12-3.)
1)
Check the filter rating label to ensure that the current,
voltage rating and part number are correct.
2)
The back panel of the wiring cabinet of board should
be prepared for the mounting dimensions of the filter.
Care should be taken to remove any paint etc. from
the mounting holes and face area around the hole of
the panel. This will ensure the best possible ground-
ing of the filter.
3)
The filter should then be securely mounted in
position, and the drive mounted to the front of the
filter with the screws provided.
4)
Connect the incoming mains supply to the filter
terminals marked "LINE" and ground cables to the
ground stud provided. Fit the Input Ferrite Ring, then
connect the filter terminals marked "LOAD" to the
mains input of the drive using a short length of
appropriate gauge wire.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Rated
Max.
Dimension
Current
Rated
L x W x H
Voltage
inches (mm)
5.5A
12.2 x 6.1 x 1.8
(310 x 155 x 45)
12A
3-phase
12.2 x 6.1 x 1.8
415 VAC (310 x 155 x 45)
35A
13.0 x 8.9 x 1.8
(330 x 225 x 45)
50A
18.9 x 9.8 x 2.6
(480 x 250 x 65)
72A
18.9 x 9.8 x 2.6
(480 x 250 x 65)
5)
6)
7)
8)
12-2
Conforms to EN55011 Class B
Mounting Dim.
X, Y
Fixing
inches (mm)
4.1 x 11.6
M5 x 12 (4)
(105 x 295)
4.1 x 11.6
M5 x 12 (4)
(105 x 295)
6.6 x 12.2
M8 x 16 (4)
(167 x 310)
7.3 x 17.8
M8 x 16 (4)
(185 x 450)
7.3 x 17.8
M8 x 16 (4)
(185 x 450)
Fit the Output Ferrite Ring as close to the drive as
possible and connect the motor. Armored or
screened cable should be used with the 3 phase
conductors only passing twice through the center
of the Output Ferrite Ring. The ground conductor
should be securely grounded at both grand
terminal in the cabinet and motor ends. The screen
should be connected to enclosure.
It is important that all lead lengths are kept as short
as possible and that incoming mains and outgoing
motor cables are kept well separated.
Segregate power cables from control wiring as
much as possible, and avoid parallel cable runs to
minimize "noise coupling". Whenever runs of power
and control cable must cross, try to achieve this at
right angles.
AF-300E$ drives should be installed, and are
designed to operate, within an electrically-shielded
metal enclosure.
Drive
Required
Sub Filter
Ferrite
Ring
OC1 (2)
Ferrite
Ring
OC2 (2)
12-001